Zeta ID2/8/M Infinity ID2 Intelligent 2 Wire 8 Zone Fire Panel in Metal Enclosure
DESCRIPTION
Zeta Alarm Systems is proud to introduce the most advanced 2 wire system on the market. We can now provide a system that gives all of the benefits associated with a ‘2 Wire’ installation (less cable, quicker installation, cost savings on labour/product) and has the facility to ‘I.D.’ the devices.
The system is built on the proven communication protocol developed by Zeta Alarm Systems and shares the same platform as our largest, most powerful system.
The ID2 can be used for new installations, as a retrofit for any conventional system or as a replacement for existing 2 wire systems when the extra features are deemed to be desirable/necessary. This is possible because the ID2 devices sit on radial circuits, thus making it easy to ‘upgrade’ a system with the facility to I.D. devices without the need to re-wire.
Enquiry Form
Zeta ID2/8/M Infinity ID2 Intelligent 2 Wire 8 Zone Fire Panel in Metal Enclosure
Zeta Alarm Systems is proud to introduce the most advanced 2 wire system on the market. We can now provide a system that gives all of the benefits associated with a ‘2 Wire’ installation (less cable, quicker installation, cost savings on labour/product) and has the facility to ‘I.D.’ the devices.
The system is built on the proven communication protocol developed by Zeta Alarm Systems and shares the same platform as our largest, most powerful system.
The ID2 can be used for new installations, as a retrofit for any conventional system or as a replacement for existing 2 wire systems when the extra features are deemed to be desirable/necessary. This is possible because the ID2 devices sit on radial circuits, thus making it easy to ‘upgrade’ a system with the facility to I.D. devices without the need to re-wire.
Key Features:
- The system meets the full requirements of BSEN5839 parts 1 and 6.
- The control panel has been designed to meet EN54 parts 2 and 4.
- Each device can be uniquely identified by the panel
- Device Count Verification
- Alarm Verification
- 2048 Event History
- ID2 Smartphone App available for iOS and Android
- Cable Break protection
- Cable Short Circuit Protection
- One man walk test facility
- Auto configuration for easy set up
- Safer than a traditional 2 wire/conventional system as it tells you exactly where the event is - no time wasted searching a whole zone
- Technical Specification
Model ID2/2 ID2/4 ID2/8
Part No. 37-660 37-661 37-663
Supply Voltage 230V AC +10% /- 15% @ 50/60 Hz
System Voltage 29V DC Nominal (19 – 30 V)
Sounder Output
Loop Powered Sounders 2 x Conventional sounder circuits
28V nominal,150mA (20-30V DC)
Fault Output 1 x Fault Relay SELV@1A (Normaly
Energised)
Fire Output 1 x Fire Relay SELV@1A
No. of Zones 2 4 8
Zone Capacity 15 Devices per Zone
Max. No. of
Detection Circuits
Radial Mode - 8 Radial Circuits
Loop Mode - 1 Loop Circuit
Max. Loop
Sounder Quantity 80 Sounders
Repeater
Connection RS485
Dimensions (mm) 370(W)
x 311(H)
x 113(D)