Gent 07011-40 Optical Beam Reflective 50-100m
‘- Combined transmitter and receiver unit in one discrete unit
– Range 50-100 Metres
– Low current consumption
– Automatic self check drift compensation
– Selectable sensitivity/threshold levels
– Selectable latching / non latching fire alarm
– LED indicators to aid the alignment process
– Optional Low Level Test Unit for UL models only
Enquiry Form
TECHNICAL SPECIFICATIONS
- Operating Range : 50 to 100 Metres
- Operating Voltage Range : 10.2V DC to 30Vdc
- Quiescent Current :
- Alarm Current : <15mA
- Power Down Reset Time : 5 seconds
- Fire Relay Contacts : Normally Open,VFCO 2A @ 30Volts DC, resistive
- Fault Relay Contacts : Normally Closed,VFCO 2A @ 30Volts DC, resistive
- Operating Temperature : -20°C to +55°C (non-condensing)
- Fire Alarm Thresholds : 1.25dB (25%), 1.87dB (35%), 3.00dB (50%)
- OpticalWavelength : 880nm
- Detector Dimensions : Width 126mm, Height 210mm, Depth 120m
- Prism Dimensions : Width 100mm, Height 100mm, Depth 9.5mm
- Weight : 0.67 kg
- LED Indications : Red LED: Indicates FIRE, Continous Amber LED: Indicates FAULT, Flashing Amber LED: Once every 10 seconds indicates normal operating mode (RV Models only), Flashing Amber LED: Once every 2 seconds indicates the compensation function has reached its limit
- Alarm Condition : Indicated by fire relay closing, Alarm may be latching or non-latching (default)
- Fault Condition : Indicated by fault relay opening
- IP Rating : IP50
- Relative Humidity : RH 0% to 93%, (non-condensing)
- Approvals/Certification : Designed, manufactured and certified to EN54-12: 2002, Use 25% and 35% (default) thresholds.The 50% threshold is recommended for hostile and extreme environments.
- CPD Reference : 0786-CPD-20045
- UL File : S3417
- Parts List : 1 x Detector Head Assembly, 4 x prism, 1 x Test Filter, 1 x Cable Interface
- Housing Construction : Flame Retardant ABS, Finish: Grey / Black