C-TEC MFP 16 Zone Conventional Fire Alarm Panel (expandable to 28 zones) Part No. FF516
-
-
- DESCRIPTION
- Microprocessor based design.
- Robust metal enclosure c/w lift off lid & heavy-duty base connections.
- 28 conventional Zone circuits.
- 4 conventional Sounder circuits.
- Separate indicators for open circuit, short circuit, head-out, sounder & battery/power supply faults.
- Non-latching class change sounder input, latching fire & non-latching fault outputs (via expansion loom).
- Zone selectable short circuit=fire facility (pre-1980 BS, no resistors in call points).
- Up to 8 two-wire Repeaters per Main panel.
- Multi-lingual variants (subject to quantities).
- Space for 2 x 12V 7Ah VRLA batteries.
- Compatible with virtually all known conventional fire detectors including C-TEC’s ActiV range.
- Designed to comply with BS 5839-4 (this panel in not compliant with EN54-2/4 and should NOT be used in new UK or European installations).
-
Enquiry Form
C-TEC MFP 16 Zone Conventional Fire Alarm Panel (expandable to 28 zones)
FF516
- Microprocessor based design.
- Robust metal enclosure c/w lift off lid & heavy-duty base connections.
- 16 conventional Zone circuits (expandable to 28).
- 4 conventional Sounder circuits.
- Separate indicators for open circuit, short circuit, head-out, sounder & battery/power supply faults.
- Non-latching class change sounder input, latching fire & non-latching fault outputs (via expansion loom).
- Zone selectable short circuit=fire facility (pre-1980 BS, no resistors in call points).
- Up to 8 two-wire Repeaters per Main panel.
- Multi-lingual variants (subject to quantities).
- Space for 2 x 12V 7Ah VRLA batteries.
- Compatible with virtually all known conventional fire detectors including C-TEC's ActiV range.
- Designed to comply with BS 5839-4 (this panel in not compliant with EN54-2/4 and should NOT be used in new UK or European installations).
Compatibility | Designed to comply with the requirements of BS5839-4 (with head-out monitoring as standard). |
Mains supply | 230V 50/60Hz. |
Mains rated current | 700mA max. |
Internal power supply | 27V nominal. |
Total output current limited to | 3A @ 230V. |
Quiescent current | 135mA (with no mains supply, fault beeper muted, no aux. output connections, EOL devices and resistors only fitted to detector and sounder loops). |
Max battery size and type | 2 x 12V 7Ah VRLA connected in series. |
No. of detector zone circuits | 28 (Max. length per circuit is 500m). |
Call point resistor value | 470 to 680Ω. |
Max. devices per detector zone | 20 detectors (max. detector current 2mA). No limit for manual call points. |
No. of conventional sounder circuits | 4 (Max. length per circuit is 500m). |
EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Max. sounder output current | 3mA (to all outputs). Outputs are fused at 1A. |
Auxiliary relays | 1 x onboard relay (1A, 30 VDC, follows sounders). |
Open collector outputs | 2 x Fire and 1 x Fault output available via optional FF574X expansion loom. Max. sink current 100mA. |
Auxiliary inputs | Class change input available via optional FF574X expansion loom. |
Indicators | Mains On; Gen Fire; Zone Fire; Zone Fault (S/C, O/C, head out, Zone disabled); Sndr Fault; Processor Fault; Batt/PSU Fault; Aux O/Ps Disabled; Fault Sounder (fault, silenced fire and delayed sounders); OMT; Sounder Walk Test |
Controls | External (key operated): Reset/Test Scroll; Silence Alarm/Fault Sounders; Evacuate; Disable. Internal: OMT; Sounder Walk Test; Sounder Isolate; Sounder Delay; S/C equals fire; Non-latching zones. |
Product dimensions (mm) | 521 W x 334 H x D 140mm. |
Construction & finish | Metal lid and base. |
IP Rating | IP30. |
Weight | 9.5kg. |
Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
Notes | One FF596T repeater transmitter PCB allows the connection of up to eight monitored MFP Repeaters (star or daisy chain wiring, two wires, one for power and one for data). |