AlarmSense Standard Rate of Rise Heat Detector
55000-190APO
- A high quality Type A1R rate of rise heat detector.
- Suitable for use with C-TEC's CFP AlarmSenSe range of 2-8 Zone Two-Wire Fire Panels.
- Housed in a pure white polycarbonate moulding.
- Fitted with two alarm LEDs to allow 360º visibility.
- Third-party certified to EN54-5 by UL International (UK) Limited.
- 9-33V DC operating voltage.
- Requires a 45681-244APO AlarmSense base.
- Can also be purchased as part of a detector/sounder or detector/sounder visual indicator base combination (see Combination AlarmSense Devices section below).
Approvals/certifications | Certified to EN54-5 by UL International (UK) Limited. |
Application/operation | Generates an alarm condition when it detects a temperature of between 84ºC & 100ºC. |
Application temperature | 55°C typical, 80°C max. |
Static response temperature | 84°C min, 100°C max. |
Supply wiring | 2-wire monitored, polarity insensitive. |
Supply/operating voltage | 9 to 33V DC. |
Quiescent current | 50µA @ 15 VDC. |
Alarm voltage | 9-33V DC. |
Alarm current | 1.5mA @ 2-8.5V; 25 +/- 2mA @ 10.5-15V; 1.5AmA @ 18-24V; 2mA @ 33V. |
Alarm reset voltage | 2V max (1 second alarm reset time). |
Product dimensions (mm) | 100mm diameter x 42m deep (detector only); 100mm diameter x 50mm deep (detector in base). |
Construction & finish | White polycarbonate. |
IP Rating | TBC. |
Weight | 100g. |
Detector
55000-391APO
- An integrating optical smoke detector.
- Responds well to slow-burning, smouldering fires.
- Suitable for use with C-TEC's CFP AlarmSense range of 2-8 Zone Two-Wire Fire Panels.
- Housed in a pure white polycarbonate moulding.
- Fitted with two alarm LEDs to allow 360º visibility.
- Third-party certified to EN54-7 by UL International (UK) Limited.
- 9-33V DC operating voltage.
- Requires a 45681-244APO AlarmSense base.
- Can also be purchased as part of a detector/sounder or detector/sounder visual indicator base combination (see Combination AlarmSense Devices section below).
Approvals/certifications | Certified to EN54-7 by UL International (UK) Limited. |
Application/operation | Generates an alarm condition when it detects a pre-set threshold of smoke penetration into the smoke chamber. |
Supply wiring | 2-wire monitored, polarity insensitive. |
Supply/operating voltage | 9 to 33V DC. |
Quiescent current | 50µA @ 15 VDC. |
Alarm voltage | 9-33V DC. |
Alarm current | 1.5mA @ 2-8.5V; 25 +/- 2mA @ 10.5-15V; 1.5AmA @ 18-24V; 2mA @ 33V. |
Alarm reset voltage | 2V max (1 second alarm reset time). |
Product dimensions (mm) | 100mm diameter x 42m deep (detector only); 100mm diameter x 50mm deep (detector in base). |
Construction & finish | White polycarbonate. |
IP Rating | TBC. |
Weight | 100g. |